Distributor stock
AFP0421|FP0 Intelligent units
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
| Product Number | FP0-TC8 |
|---|---|
| Part Number | AFP0421 |
| Product | Thermocouple Unit |
| Details | Screw terminal block |
| Product Name | FP0 Intelligent units |
Distributor stock ? Stock status at external e-commerce sites handling Panasonic Industry products.
Contact Us
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
| Item | Specifications |
|---|---|
| Part Number | AFP0421 |
| Product Number | FP0-TC8 |
| Product Name | Thermocouple Unit |
| Product details | Screw terminal block |
| Number of input points | 8-channel (The number of input points can be changed 2, 4, 6 and 8 channels.) |
| Input range | Range for K and J -100.0 to 500.0 ℃/-148.0 to 790.0 ℉ (Note 1)(Note 2) Range for T -100.0 to 400.0 ℃/-148.0 to 752.0 ℉(Note 2) Range for R 0 to 1500.0 ℃/32.0 to 1590.0 ℉(Note 1) Notes: 1) The measurement range available for degree Celsius is not available for degree Fahrenheit, of which the upper-limit measurement is set lower than degree Celsius, since the digital value (temperature value displayed) for degree Fahrenheit is bigger than that for degree Celsius. 2) If the measurement temperature is below -50 ℃/-58 ℉, temperature measurement is possible, but accuracy cannot be guaranteed. |
| Digital output | K and J (when using ℃): K -1000 to K5000 K and J (when using ℉): K -1480 to K7900 (Note 1) (When range over using ℃: K-1001, K5001 or K8000) (When range over using ℉: K-1481, K7901 or K8000) (When the thermocouple broken: K8000) (Note 2) (Until the temperature can be measured at the initial startup: K8001) (Note 3) T (when using ℃): K -1000 to K4000 T (when using ℉): K -1480 to K7520 (When range over using ℃: K -1001, K4001 or K8000) (When range over using ℉: K -1481, K7521 or K8000) (When the thermocouple broken: K8000) (Note 2) (Until the temperature can be measured at the initial startup: K8001) (Note 3) R (when using ℃): K0 to K15000 R (when using ℉): K320 to K15900 (Note 1) (When range over using ℃: K 0, K15001 or K16000) (When range over using ℉: K 0, K15901 or K16000) (When the thermocouple broken: K16000) (Note 2) (Until the temperature can be measured at the initial startup: K16001) (Note 3) Notes: 1) The measurement range available for degree Celsius is not available for degree Fahrenheit, of which the upper-limit measurement is set lower than degree Celsius, since the digital value (temperature value displayed) for degree Fahrenheit is bigger than that for degree Celsius. 2) When the thermocouple is broken, the digital value will become K8000 or K16000 within 70 seconds since broken. Practice in the ladder program a process for avoiding a risk, would be resulting from a broken thermocouple, and exchange the thermocouple. 3) Until the conversion data will be ready after the initial startup was made, the digital value shows K8001 or K16001. Those are not a temperature data. Create a ladder program, so that they are not acquired as a temperature data. |
| Resolution | 0.1 ℃ |
| Sampling cycle | 300 ms: when using 2 channels for an input points (The settings of the input channel selection switch.) 500 ms: when using 4 channels for an input points (The settings of the input channel selection switch.) 700 ms: when using 6 channels for an input points (The settings of the input channel selection switch.) 900 ms: when using 8 channels for an input points (The settings of the input channel selection switch.) Notes: Conversion values for 6-time measurements (6 from the latest 8 measurements, excluding the max. and min.) are averaged, so that it takes time for the digital value to be displayed due to the rapid temperature change. |
| Indication accuracy | Range for K, J and T ±0.2 % F.S. (at +25 ℃ +77 ℉) ±0.4 % F.S. (at 0 to +55 ℃ +32 to +131 ℉) Range for R ±0.2 % F.S. (at +25 ℃ +77 ℉) ±0.4 % F.S. (at 0 to +55 ℃ +32 to +131 ℉) Notes: If the measurement temperature is below -50 ℃/-58 ℉, temperature measurement is possible, but accuracy cannot be guaranteed. |
| Reference junction compensation accuracy | ±1.0 ℃ |
| Input impedance | 1 MΩ or more |
| Insulation method | ・Between thermocouple input terminals and FP0 internal circuits : Photo-coupler insulation, DC/DC converter insulation ・Between thermocouple input terminal channels: PhotoMOS relay insulation |
| Number of I/O contact points | 32 input contact points Notes: The control unit reads the data for 2 channels per 1 scan by the control unit. Read data by utilizing the sample program given in the product specifications and manual. |
Check Stock at Distributors
View availability from authorized distributors in your selected region.
Product Number FP0-TC8
Part Number AFP0421
Disclaimer
Distributor stock information is provided for reference only and may change without notice. Please confirm availability, MOQ, shipping options, lead times, pricing, and purchase conditions directly with each distributor.
Powered by
